CFM Calculator: How Many CFM Do You Need for Your Room?

Enter your room size and pick what the airflow is for (air purifier, bathroom fan or kitchen exhaust) to see how many CFM you need, with the formula and the source behind every target.

I want to find
Units

Airflow you need

– CFM

Room volume
–
Floor area
–
In cubic meters per hour
–

How many CFM do you need? It depends on what the airflow is for. An air purifier is sized by how many times an hour it cleans the room’s air, a bathroom fan by floor area or fixtures, and a range hood by a fixed minimum. This calculator covers all three: enter the room, pick the job and it shows the cubic feet per minute (CFM) to look for, plus the source behind the number.

You can also run it the other way round: enter a CFM and see how many air changes per hour it gives the room.

How the calculator works

The core formula is the one CDC/NIOSH uses for air changes:

CFM = room volume (cu ft) × air changes per hour ÷ 60

Air changes per hour = CFM × 60 ÷ room volume (cu ft)

Room volume is length × width × ceiling height. Metric sizes are converted to feet first, because airflow ratings in the US are published in cubic feet per minute; the result is also shown in cubic meters per hour (1 cfm = 1.699 m³/h, the conversion AHAM uses). For “how many CFM do I need”, the result is rounded up to the next whole cfm.

The presets

JobTargetSource
Air purifier, everyday4.8 air changes per hourAHAM: the room size on the box is based on 4.8
Air purifier, CDC5 air changes per hourCDC/NIOSH “aim for 5” for occupied rooms
Air purifier, wildfire smoke7.5 air changes per hourAHAM: smoke CADR at least equal to the floor area (8 ft ceiling)
Bathroom fan, up to 100 sq ft1 cfm per sq ft, at least 50 cfmHVI (1 cfm/sq ft); ASHRAE 62.2 (50 cfm minimum)
Bathroom fan, over 100 sq ft50 cfm per toilet, shower or tub; 100 cfm per jetted tubHVI
Kitchen, vented range hood100 cfmASHRAE 62.2
Kitchen, other exhaust fan300 cfm, or 5 air changes per hour in an enclosed kitchenASHRAE 62.2
Kitchen, continuous exhaust5 air changes per hour of the kitchen’s volumeASHRAE 62.2 (enclosed kitchens only)

For the bathroom, the calculator takes the larger of HVI’s figure and ASHRAE’s 50 cfm. A bathroom fan that runs continuously instead of being switched on needs only 20 cfm under ASHRAE 62.2.

Worked examples

All rooms have 8 ft ceilings unless noted.

RoomJobCalculationResult
Bedroom, 12 x 12 ft (1,152 cu ft)Air purifier, everyday1,152 × 4.8 ÷ 60 = 92.293 cfm smoke CADR
Same bedroomAir purifier, CDC1,152 × 5 ÷ 6096 cfm
Same bedroomAir purifier, wildfire smoke1,152 × 7.5 ÷ 60144 cfm (equal to the 144 sq ft floor, as AHAM’s rule says)
Living room, 20 x 15 ft, 9 ft ceiling (2,700 cu ft)Air purifier, everyday2,700 × 4.8 ÷ 60216 cfm
Same living roomAir purifier, wildfire smoke2,700 × 7.5 ÷ 60 = 337.5338 cfm
Bedroom, 5 x 4 m, 2.5 m ceiling (50 m³ = 1,766 cu ft)Air purifier, CDC1,766 × 5 ÷ 60 = 147.1148 cfm (251 m³/h)
Bathroom, 8 x 5 ft (40 sq ft)Bathroom fanHVI 40 cfm; ASHRAE minimum 5050 cfm
Bathroom, 9 x 10 ft (90 sq ft)Bathroom fanHVI 1 cfm × 90 sq ft90 cfm
Bathroom, 20 x 12 ft, tub, shower and toiletBathroom fan50 + 50 + 50150 cfm
Kitchen, 12 x 10 ft (960 cu ft), enclosedKitchenRange hood minimum; 960 × 5 ÷ 60 = 80100 cfm hood, or 80 cfm continuous

The 40 sq ft and 20 x 12 ft bathrooms are HVI’s own examples, so you can check them against the source. The metric example shows the conversion: 5 × 4 × 2.5 m is 50 m³, or about 1,766 cubic feet.

Going the other way: a purifier with a smoke CADR of 200 cfm in a 15 x 12 ft room (1,440 cu ft) gives 200 × 60 ÷ 1,440 = 8.3 air changes per hour. One rated at 233 cfm in a 20 x 15 ft room (2,400 cu ft) gives 5.8, enough for CDC’s 5 but not for AHAM’s 7.5 during wildfire smoke.

For air purifiers, CFM means CADR

A purifier’s fan airflow is not the same as the clean air it delivers. CADR (clean air delivery rate) is measured under ANSI/AHAM AC-1: the particle decay with the purifier running, minus natural decay, times the volume of the test chamber. So it already accounts for the filter, and it’s the CFM that counts toward air changes. Use the smoke CADR, which covers the smallest particles. Our explainer on what CADR means covers the three ratings.

Two cautions:

  • CADR is measured on the highest fan speed. EPA notes that CADR at lower settings is usually not published and can be much lower. If the purifier will run on a quiet setting, choose one rated above the result.
  • The presets assume one well-mixed room. Doors, furniture and corners slow mixing. Our air changes per hour calculator shows how long particles take to clear at a given rate, and the air purifier size calculator turns your room into the room-size rating printed on the box.

During smoke events, AHAM’s stricter wildfire rule (CADR at least equal to the floor area) is the preset to use; EPA’s own wildfire advice is a smoke CADR of at least two-thirds of the floor area. Our guide to wildfire smoke indoors covers sealing up a clean room.

Bathroom and kitchen exhaust

Exhaust fans remove moisture and odors at the source by sending air outdoors, which is why they come first in our guide on how to reduce humidity in your house. An air purifier can’t do that job: it filters particles and leaves the moisture behind, as our look at the best bathroom air purifier explains.

  • Bathrooms. HVI’s 1 cfm per square foot works out to about eight air changes per hour with an 8 ft ceiling. In bigger bathrooms, HVI suggests either one fan sized for the total or a 50 cfm fan over each fixture, and leaving the fan on for 20 minutes after using the bathroom.
  • Kitchens. ASHRAE 62.2 sets 100 cfm for a vented range hood regardless of kitchen size. Other kitchen exhaust fans, including downdraft vents, have to move more: 300 cfm, or 5 air changes per hour in an enclosed kitchen. Continuous kitchen exhaust is only allowed in an enclosed kitchen; an open-plan kitchen needs a fan you switch on.

These are minimum rates from ASHRAE 62.2 and HVI’s recommendations. Your local building code may set its own, and for a new installation it’s worth checking with the installer.

If a basement or closed room stays damp even with fans, a dehumidifier is the next step: the dehumidifier size calculator turns room size and dampness into pints per day.

Frequently asked questions

How do you calculate CFM for a room?

Multiply the room volume in cubic feet by the air changes per hour you want and divide by 60. A 12 x 12 ft room with an 8 ft ceiling (1,152 cu ft) at 5 air changes per hour needs 1,152 × 5 ÷ 60 = 96 cfm.

How many CFM do I need for an air purifier?

For everyday use, AHAM's room sizing works out to 4.8 air changes per hour, so a 12 x 12 ft bedroom with an 8 ft ceiling needs a smoke CADR of about 93 cfm. CDC's 5 air changes per hour gives 96 cfm, and AHAM's wildfire-smoke level of 7.5 gives 144 cfm. Compare these with the smoke CADR, not the fan's airflow.

What CFM bathroom fan do I need?

HVI recommends 1 cfm per square foot for bathrooms up to 100 sq ft, and ASHRAE 62.2 sets 50 cfm as the minimum for a fan you switch on and off, so most small bathrooms need 50 cfm or more. Above 100 sq ft, HVI adds 50 cfm per toilet, shower or tub and 100 cfm per jetted tub.

How many CFM does a range hood need?

ASHRAE 62.2 sets 100 cfm as the minimum for a vented range hood. Other kitchen exhaust fans, including downdraft vents, need 300 cfm, or in an enclosed kitchen a capacity of 5 air changes per hour.

What is the difference between CFM and CADR?

CFM (cubic feet per minute) is any airflow. CADR is the clean air an air purifier delivers, also in cubic feet per minute, measured on the highest speed under AHAM's test. It accounts for how well the filter works, so it is the number to use for purifier sizing.

Related guides